Document No: LT0119 F3200 Operator's Manual
Operating Instructions - Zone Functions
Issue 2.04 29 July 2002 Page 7-9
7.4 ZONE AUTO-RESET MODE
7.4.1 FUNCTION
Auto-Reset mode allows testing of all detectors on an Alarm Zone Circuit without the
need for a second person resetting alarms at the FIP.
Auto-Reset mode isolates the zone from its outputs, and automatically resets detectors
in alarm on the circuits being tested.
In Auto-Reset mode the alarm bell will operate for 2 seconds when the zone goes into
the alarm condition unless the bells output is isolated, or the zone is not mapped
(programmed) to operate the bells, or the zone is isolated.
For network system, to auto-reset test a zone on a remote panel, refer to Section
11.10.6. To auto-reset test a local zone, follow this section.
7.4.2 OPERATING SEQUENCE
To put a single zone into Auto-Reset mode
From the base display, press:
to Auto-Reset test Zone nn.
From a zone status display, to Auto-Reset test the displayed zone press:
followed by