F3200 Operator's Manual Document No: LT0119
Operating Instructions - Relay/Output Functions
Page 8-8 29 July 2002 Issue 2.04
8.6 ANCILLARY RELAY STATUS RECALL
8.6.1 FUNCTION
To display the status of a local ancillary relay. For network systems, to display the status
of an ancillary relay on a remote panel use a zone recall command. Refer Section
11.10.
8.6.2 OPERATING SEQUENCE
To display the status of a local ancillary relay, from the base display press:
to select ancillary relays
then press numeric key "1", "2" or "3" to select the desired ancillary relay.
The programmed name for the relay will be show on the top line and the status of the
relay will be shown on the bottom line of the display as follows:
deactivated - if the relay is de-energised
activated - if the relay is energised
normal - no supervision fault
fault - supervision fault
open circuit - supervision fault
short circuit - supervision fault
isolated - the relay is isolated
deisolated - the relay is not isolated
SilAlms - For an NDU in New Zealand mode, this will be shown if the Silence
Alarms keyswitch is operated.
NetSil - For a networked system, this is shown if the relay is inhibited (silenced)
by an isolate state on another panel.
The "RESET", "ISOLATE" and "TEST" keys may be used from this display and "NEXT"
and "PREV" may be used to step through the three ancillary relays.