F3200 Operator's Manual Document No: LT0119
General Display & Keypad Operation
Page 4-2 29 July 2002 Issue 2.04
4.1 INTERPRETING THE LEDS
4.1.1 OPERATOR DISPLAY LEDS
The description of LED states in this section applies to both non-networked and
networked F3200 panels and also to the NDU.
The 8 LEDs on the Operator Display Panel indicate status as follows:
LED off (unlit) for function off;
LED on (steady) for function on;
The ALARM, CHGR/BATT FAULT and BELLS ISOL LEDs indicate further
information by flashing;
For Fire Alarm System normal only the MAINS ON LED should be on;
All LEDs (except MAINS ON) flash rapidly for 2 seconds on FIP power up, and at
1Hz for LED Test.
LED
State Interpretation
ALARM Flashing Unacknowledged alarm in FFCIF alarm queue.
Steady If there are no unacknowledged alarms; and the alarms
total on the base display is not zero (includes isolated
zones).
ISOLATED Steady If the isolates total on the base display is not zero.
FAULT Steady If the faults total on the base display is not zero.
MAINS ON Steady Mains power is present.
CHGR/BATT Flashing Battery test failed (battery capacity less than 45%)
FAULT Note, while the LED is flashing Battery Test cannot be
re-started.
The LED will flash for 60 seconds then turn off.
Steady Battery charger voltage is too high or low.
SYSTEM Steady System Fault, e.g. electronics faulty, module
FAULT unplugged, keypad unplugged or all zones isolated.
ANCILLARY Steady Ancillary Relay or Module Relay is isolated.
ISOLATED (includes Anc 3 if programmed as Anc3 rather than
Bells).
BELLS Steady Bells output is locally isolated.
ISOLATED Flashing For a network system if the bells output is silenced due
to network silence. Refer to Section 11.4.