Document No: LT0119 F3200 Operator's Manual
Network Systems
Issue 2.04 29 July 2002 Page 11-17
11.9 REMOTE RELAY & OPEN COLLECTOR
OPERATION & ZONE MAPPING
An F3200 panel maps its inputs and outputs to zones as follows so that they can be
accessed across the network using the zone number.
Zones 1-64 - Alarm zones 1-64
Zones 65-128 - Module relays 1-64
Zones 129-192 - Open collectors 1-64
Zone 193 - Bells
Zone 194 - Ancillary relay 1
Zone 195 - Ancillary relay 2
Zone 196 - Ancillary relay 3 if not bells
Zone 197 - Plant isolate
For example, to recall the status of module relay 3, a recall of zone 67 would be done.
When a recall command is done to search for zones in a particular condition, the recall
includes a search of all the above zones except for open collectors which are never
included in zone searches.
Note that local module relays, open collectors and ancillary relays are also accessible by
pressing the RELAY key from the base display. This requires the entry of an actual relay
number rather than a zone number.
Module relays and ancillary relays on a remote F3200 panel (or NDU) may be recalled,
isolated, de-isolated, reset or tested using a zone recall, isolate, de-isolate, reset or test
command (as described in Section 11.10) with the appropriate zone number determined
from the mapping above.
To test a remote relay or open collector, use a zone operate test command, (option 3
from the test menu), as described in Section 11.10.6, using a zone number determined
from the mapping above.