F3200 Operator's Manual Document No: LT0119
System Specifications
Page 3-10 29 July 2002 Issue 2.04
MAF/PSU OUTPUTS (CONTINUED)
Ancillary & Bells
Number 3 relays
Anc 1, Anc 2 1 Pole changeover contacts
Voltage-free
Rating ELV only
30V, 2Adc resistive
30V, 1Adc inductive
Operation Programmable
Default Active on any unisolated Zone Alarm.
Supervision Separate terminal, 2 modes, programmable
(refer to Technical or Installation manual)
Anc 3/Bells 1 relay, 2 pole
Link selectable function
Standard Format Bells, Switched 24Vdc output
2 terminals, Bells +, -
Rating 24V, 1.5A Inductive Bells
Supervision Programmable, requires diode at each device
Number of Circuits Resistor End of Line (each circuit)
1 3k3
2 6k8
3 10k
3.6 SERIAL COMMUNICATIONS
RZDU Comms
Tx, Rx, 0V 3 Wire (+VBF2 also available). Terminals on MAF/PSU.
Transmission 1200 Baud, Vigilant F4000 RZDU Protocol.
Printer/Programmer Port
Form Pseudo RS232 Rx, Tx, 0V signals only
Transient Protection Allows external wiring
Transmission 9600 Baud (programmable)
ASCII Xon, Xoff Protocol
Termination 4 Way .156" male molex (J1 on Controller/Display).
Standard cables with miniature D connectors available.