F3200 Operator's Manual Document No: LT0119
Operating Instructions - Brigade Functions
Page 5-10 29 July 2002 Issue 2.04
5.8 RECALLING ALARMS
5.8.1 FUNCTION
It is possible for there to be un-isolated, acknowledged alarms present in the FFCIF
queue, but the display NOT
be in FFCIF mode. The FFCIF can be recalled, and thus put
the display into FFCIF mode.
If a zone is in alarm but is isolated, it will not be in the FFCIF queue. It can be recalled
as "Alarms". (Refer also to Section 7.5).
5.8.2 OPERATING SEQUENCES
Press the "CLEAR ESC" key until the base display is shown.
Press the "RECALL" key followed by the "1" key to select option 1:Alarms list
for non-isolated alarms
NOTE:
If there are no alarms in the FFCIF alarm queue, then the LCD will briefly display "Alarm
queue is empty" and revert to the base display.
OR
for isolated alarms
Press the "RECALL" key followed by the "4" key to select option 4:Alarm to show all
zones in alarm (includes isolated zones and zones not mapped to the FFCIF).
5.8.3 NON-FFCIF ALARMS
It is possible to have zones not mapped to the FFCIF (i.e. display only zones, e.g. flow
switch). These might be displayed on LEDs only.
If such a zone goes into alarm the buzzer will not sound, the LCD will not automatically
display the zone, and the FFCIF ALARM LED will not
be on. The base display will show
this in the "Other" total, not "Alarm". The zone can still be found by Recall Alarms
(RECALL 4), as above, or by Recall Other.
It is also possible to have "status only" zones which do not even appear in the "Other"
total. These may only be viewed by pressing "Zone", followed by the zone number.