Document No: LT0119 F3200 Operator's Manual
Operating Instructions - Brigade Functions
Issue 2.04 29 July 2002 Page 5-9
5.7 EXITING FFCIF MODE
5.7.1 FUNCTION
While in FFCIF mode, access to all other functions and displays is prevented. On
occasion it may be necessary to recall an Isolated Alarm, de-isolate a zone or perform
some other function. To do so, FFCIF mode must be exited.
FFCIF mode can be exited only when ALL
alarms in the list have been acknowledged.
When FFCIF mode is exited, the LCD reverts to the display it had before the alarms
occurred. At that stage, the required functions can be performed e.g. Recall Alarms.
5.7.2 OPERATING SEQUENCE
Press the "CLEAR ESC" key once:
- If all alarms are acknowledged, FFCIF mode is exited and the
LCD reverts to the display state that was showing before the
alarms occurred.
- If any alarms are NOT
acknowledged, the sounder will produce
an error tone, and FFCIF mode will not be exited. It is
necessary to acknowledge all alarms before FFCIF mode can
be exited.
NOTE To re-enter FFCIF mode to view the list of alarms, use the Recall Alarms
list command sequence. Refer to Section 5.8 Recalling Alarms.