Document No: LT0119 F3200 Operator's Manual
Network Systems
Issue 2.04 29 July 2002 Page 11-27
11.11 POINT RECALLS & COMMANDS
If any devices on the network support analogue addressable points then they can be
accessed from an F3200 panel or NDU (if so programmed). The status of a remote point
can be recalled, and commands of isolate, de-isolate, point reset, reset tracking or reset
history may be initiated.
The common isolate LED on the operator display panel will flash at 2Hz if there are any
isolated points on a remote SID. When the status of a remote SID is being displayed (by
recall system faults - Sections 11.6.1 and 11.6.2) the text CmnPtl
will be shown on Page
3 of the list if the remote SID has any isolated points. Refer to the Operator Manual for
the remote panel to determine the meaning of point values and numbering.
11.11.1 POINT STATUS RECALL
There are three different status displays which may be selected for a point. These are:
1. Point Status; showing Normal, Fault, Alarm, Isol, Node Fault, Pre-Alarm,
Maintenance Alert.
2. Analogue values; showing CV, TV, HH, HL.
3. Analogue levels; showing current level (CL), pre-alarm sensitivity (PS), alarm
sensitivity (AS).
4. Dirty Detectors; shows the % dirty value as a percentage plus the tracked
value (TV), clean air max (CM), the upper tracking limit (UT)
and the alarm sensitivity (AS) of the detector.
To recall the status of a specific point, from the base display, press either:
OR
If the panel does not have a POINT key then the RELAY key should be used.
Depending on the type of panel, either a menu of options will appear or the operator will
be prompted to enter a point number.
If a menu appears, select option 4: Network point, and then enter a point number.