F3200 Operator's Manual Document No: LT0119
Network Systems
Page 11-18 29 July 2002 Issue 2.04
11.10 NETWORK ZONE RECALLS & COMMANDS
11.10.1 ZONE RECALLS
Section 4.2.2 describes how to recall alarms, faults, isolates, and "others". For a network
panel this will search all programmed devices on the network as well as the local panel.
Network zones may also be recalled and searched as described in the following
sections.
11.10.2 LOCAL OR NETWORK ZONE STATUS RECALL
To recall a specific zone's status, press:
where nnnnn is a network zone number.
The first line of the LCD displays the zone number and any zone name programmed for
that zone.
Note that there may be a delay between requesting a network zone status and display of
the true status, due to network delays. In this case, the panel will display default text, ie.
just the network zone number, until the data is received. The display will update with the
zone name and status when it is received.
The second line displays the zone alarm type text for that zone, followed by its status.
The status consists of any of the following:
Alarm - the zone is in alarm.
Operate - the ACZ is operated.
Fault - the zone is in fault.
Isolate - the zone is isolated.
Test - the zone is currently being tested.
ARst - the zone is currently being auto reset tested.
Normal - the zone is normal.
To view other zones in the same condition press the NEXT or PREV keys.