F3200 Operator's Manual Document No: LT0119
Operating Instructions - Brigade Functions
Page 5-12 29 July 2002 Issue 2.04
5.10 FFCIF MODE 2 OPERATION
FFCIF mode 2 should only be configured (by programming) in a FIP which has LED
Display Bds fitted (i.e. an LED display for each zone).
Operation in FFCIF mode 2 is different to that of mode 3 in the following ways.
When an alarm occurs on any zone mapped to the MAF, the LCD immediately displays:
Zones are in alarm! Press RECALL to view
ACK = Silence RESET = Reset ISOL = Isolate
.. (1)
Pressing "ACK" silences the buzzer and acknowledges all unisolated alarms.
Pressing "RESET" will silence the buzzer (if still sounding) and (without prompt) reset all
unisolated alarms. The LCD then returns to the display it had before the alarm occurred.
Pressing "ISOL" will silence the buzzer (if still sounding) and (without prompt) isolate all
unisolated alarms. The LCD then returns to the display it had before the alarm occurred.
Pressing "RECALL" will silence the buzzer (if still sounding) and immediately cause the
first alarm to be displayed. Operation is the same as for mode 3 described in Section
5.1. I.e. alarms must be individually acknowledged, stepped through with "NEXT",
"PREV", etc. Pressing "CLEAR ESC" returns the LCD to the display it had before the
alarm occurred only if there are no unacknowledged alarms. Pressing "RECALL" again
will return the LCD to display (1) above.