EasyManua.ls Logo

Tyco F3200 - General

Tyco F3200
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
F3200 Operator's Manual Document No: LT0119
System Specifications
Page 3-2 29 July 2002 Issue 2.04
3.1 GENERAL
3.1.1 FIP PART NUMBER & DESCRIPTION
FP0550, F3200 FIP, NO CARDFRAME, 24 ZONE MAX, 1931-15
Includes: Full size cabinet
Controller/Display with Operator Display & Keypad
MAF/PSU (includes 7 relays, 3A Battery Charger)
1 x 8 Zone Module with standard EOLRs
Modules fit to cabinet rear wall (up to 3 modules max)
FP0551, F3200 FIP, C/W CARDFRAME, 64 ZONE MAX, 1931-16
Includes: Full size cabinet
Controller/Display with Operator Display & Keypad
MAF/PSU (includes 7 relays, 3A Battery Charger)
Cardframe (can house up to 8 modules)
1 x 8 Zone Module fitted in cardframe
includes standard EOLRs
3.1.2 SYSTEM EXPANSION
Expansion of FP0550 and FP0551 is by adding 8 way modules.
FP0553, F3200 8 ZONE INPUT EXPANSION KIT
Includes: 8 Zone Module
FRC
8 x EOLR (std)
FP0554, F3200 8 RELAY EXPANSION KIT
Includes: 8 Relay Module
FRC
8 x Minijump links (for supervision selection)
3.1.3 CONTROLS
KEYPAD
Type : Polyester Membrane
Keypress : Buzzer gives short "beep" for valid keypress
Number of
Keys : 34 (plus 5 concealed with no function)
FFCIF Keys : ACK; RESET; ISOL; BRIG TEST; NEXT
4x4 Keypad : Digits 0-9; Clear/Esc; Enter; 4 x Logic Keys
NDU NZ MODE KEYSWITCHES
Brigade Functions - Trial Evacuation
- Silence Alarms
- Services Restore