Document No: LT0119 F3200 Operator's Manual
System Specifications
Issue 2.04 29 July 2002 Page 3-3
CONTROLS (CONTINUED)
KEYPAD FUNCTIONS
Zone Functions - Alarm and Fault Test
- Isolate, Reset, Recall
- Auto-Reset Test Mode
Ancillary Functions - Test, Isolate, Reset, Recall
Relay Functions - Test, Isolate, Reset, Recall
System Functions - Battery Test, Buzzer Test, Display Test
- System Test
- Bell Test, Bell Isolate
- Recall : Alarms, Faults, Isolates, System Faults, History
- Set time and date
- Program and view parameters
- Print and save database
Brigade Functions - Acknowledge Alarms
- View alarms (Next & Prev)
- Reset acknowledged zones in alarm
- Isolate acknowledged zones in alarm
- Brigade Test
BUZZER (INTERNAL SOUNDER)
Mounted on Controller/Display pcb
Tone Steady : Fault, System Fault
Unisolated zone (note 1) or relay supervision fault (note 2)
Sounder re-sounds 8 hours after silence.
Pulsing 2Hz : Alarm
Unisolated zone alarm (note 1)
Slow Pulse : Door closed with Database Write Enabled (Lk7) or zones in alarm
test or fault test.
Cadence : Zone or Auto-Test failed (note 3)
Short Pulse : Valid keypress
Long Pulse : Invalid keypress
Notes:
1. For zones not mapped to MAF (status only) the buzzer does not turn on
(dependent also on programming of FFCIF).
2. For relay supervision not mapped to MAF the buzzer does not turn on.
3. Cadence is repeated fast pulses with a pause.