Model WS Specific Application Window Sprinklers
Horizontal and Pendent Vertical Sidewall
5.6 K-factor
Page 1 of 8 MAY 2014 TFP620
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
General
Description
The TYCO Model WS Specic
Application Window Sprinklers are fast
response, glass bulb-type spray sprin-
klers available in Horizontal Sidewall
and Pendent Vertical Sidewall models.
These sprinklers are the rst to be
specically Listed to provide complete
wetting and coverage for heat strength-
ened, tempered, or ceramic glass
windows using closed sprinklers.
As part of the testing, the gas ow
required to achieve the time/temper-
ature relationship specied in ASTM
E119 was established in a test furnace
without sprinkler protection. A window
assembly protected with the TYCO
Model WS Window Sprinklers was
then installed in the test furnace, and
the same gas ow conditions were
maintained for a two-hour test period.
No cracking or visible damage to the
window was permitted during the test
period, even when a hose stream was
directed at the window.
The success of the Model WS Window
Sprinklers is based on their fast
response thermal sensitivity and on
their specially designed deectors that
ensure that the spray pattern wets the
entire surface of the window.
Based on successful testing, the
Model WS Window Sprinklers can be
used as interior protection of windows
or glazing in a sprinklered building or
non-sprinklered building in accordance
with Section 104 of the IBC (Alternate
Materials, Design and Methods of
Construction and Equipment”). Also,
the Model WS Window Sprinklers
can be used as an open sprinkler for
“Outside Sprinkler Protection against
Exposure Fire”, using the design
requirements of NFPA.
As with any specic application sprin-
kler, the installation instructions
included in this data sheet must be
precisely followed. If there are addi-
tional local or jurisdictional installation
standards/codes for window sprinklers
on glazed window systems, this docu-
ment does not relieve the designer/
installer from these requirements.
Consult your local jurisdiction to verify
if or when these additional guidelines
must be followed.
NOTICE
TYCO Model WS Specific Application
Window Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
recognized by the approval agency, in
addition to the standards of any author-
ities having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system and
devices in proper operating condition.
The installing contractor or manufac-
turer should be contacted with any
questions.
Sprinkler
Identification
Number (SIN)
TY3388 - Horizontal Sidewall
TY3488 - Pendent Vertical Sidewall
TY3388 is a re-designation for C3388
TY3488 is a re-designation for C3488
Question and Answer IconNeed help?

Do you have a question about the Tyco WS and is the answer not in the manual?

Tyco WS Specifications

General IconGeneral
BrandTyco
ModelWS
CategoryFire Alarms
LanguageEnglish

Summary

General Description

Sprinkler Identification Number (SIN)

Identifies the specific models TY3388 and TY3488, relating them to previous designations.

Notice

Technical Data

Approvals and Listings

Lists UL, C-UL, NYC MEA, and ULC approvals, applicable to specific design criteria.

Physical Characteristics

Details the materials used for each component of the sprinkler.

Operation

Design Criteria

Area of Use and Application

Defines where and how the sprinklers can be used for fire separation and exposure protection.

Glass, Frame, and Mullion Requirements

Specifies compatible glass types, frame seals, and mullion/joint requirements for installation.

Sprinkler Spacing and Placement

Details maximum/minimum distances between sprinklers and from mullions, and placement relative to glass.

Deflector and Clearance Specifications

Defines required deflector positioning and minimum clearance from combustible materials.

System and Hydraulic Considerations

Covers hydraulic calculations, water supply, and system protection types for various scenarios.

Water Demand and Flow Requirements

Water Supply Duration and Flow Rates

Outlines requirements for water supply duration and minimum flow per sprinkler based on spacing.

Pressure Limitations

Specifies the maximum allowable pressure for horizontal and vertical sidewall sprinklers.

Installation Instructions

General Installation Guidelines

Provides pre-installation checks, torque specifications, and orientation guidance for both sprinkler types.

Care and Maintenance

Sprinkler Inspection and Replacement

Details conditions requiring sprinkler replacement, such as damage, corrosion, or cracked bulbs.

Owner Responsibilities

Defines the owner's role in system inspection, testing, and maintenance per standards.

Ordering and Warranty Information

Product Ordering Details

Specifies how to order window sprinklers, including product name, P/N, temperature, and finish.

Limited Warranty Terms

Directs users to the Tyco Fire website for warranty terms and conditions.