EasyManua.ls Logo

Tyco F3200 - Open Collector Status Recall or Test

Tyco F3200
150 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
F3200 Operator's Manual Document No: LT0119
Operating Instructions - Relay/Output Functions
Page 8-12 29 July 2002 Issue 2.04
8.10 OPEN COLLECTOR STATUS RECALL OR TEST
8.10.1 FUNCTION
To view the state of a local open collector output. A test command may be used to turn
on an open collector output for five seconds if not already on.
For network systems, to recall or test an open collector output on a remote panel, use a
zone recall command or a zone operate test command. Refer to Section 11.10.
8.10.2 OPERATING SEQUENCE - STATUS RECALL
To recall a local open collector output, from the base display press:
to select open collector outputs, then press
to recall open collector output nn status.
The display will show the open collector number on the top line and the bottom line will
show either activated or deactivated according to whether the output is currently on or
off.
The "NEXT" and "PREV" keys may be used to step through the open collector outputs.
Press the "CLEAR ESC" key to return to the base display.
8.10.3 OPERATING SEQUENCE - OPEN COLLECTOR TEST
From an open collector status recall selected as described above, press:
to turn the open collector output on for five seconds or " ESC"
to abort.
If the open collector output is already on it will not be affected by the test.
If an open collector output is controlled by default logic of zone alarm then the output can
be turned off, if it is on, by isolating the corresponding zone.

Table of Contents

Other manuals for Tyco F3200

Related product manuals