Document No: LT0119 F3200 Operator's Manual
Operating Instructions - Relay/Output Functions
Issue 2.04 29 July 2002 Page 8-7
8.5 MODULE RELAY TEST
8.5.1 FUNCTION
To briefly turn on a relay output (i.e. for five seconds).
If the relay is isolated the test command will not energise the relay.
If the relay is already energised (because an output logic equation requires it to be on)
then it will remain energised and is not affected by the test.
For network systems, to test a relay on a remote panel use a zone operate test
command - refer to section 11.10.
8.5.2 OPERATING SEQUENCE
To test a local module relay, from the base display press:
to select module relays
then press
to test relay nn
or
to test the range of relays nn to mm inclusive.
Press to apply the test.
The relays will be energised (if not isolated) for five seconds, or until "ACK" is pressed,
and then de-energised.
8.5.3 NOTES
Depending on programming, a test command may not be allowed on particular relays, in
which case, the message “This relay may not be tested” will appear when an attempt is
made to test it.