EasyManua.ls Logo

Tyco F3200 - Ancillary Relay Reset Supervision Fault

Tyco F3200
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
F3200 Operator's Manual Document No: LT0119
Operating Instructions - Relay/Output Functions
Page 8-10 29 July 2002 Issue 2.04
8.8 ANCILLARY RELAY RESET SUPERVISION FAULT
8.8.1 FUNCTION
To reset a latched supervision fault on a local ancillary relay.
For network systems, to reset a latched supervision fault on an ancillary relay on a
remote panel, use a zone reset command. Refer Section 11.10.
8.8.2 OPERATING SEQUENCE
To reset a latched supervision fault on a local ancillary relay, from the base display
press:
to select ancillary relays
then press numeric key "1", "2" or "3" followed by the ENTER key to select the desired
ancillary relay. Then press:
to reset the fault.
If the fault is still physically present on the relay wiring then the relay status will remain in
fault.