Document No: LT0119 F3200 Operator's Manual
Operating Instructions - Brigade Functions
Issue 2.04 29 July 2002 Page 5-11
5.8.4 OPERATING SEQUENCES
Press the "RECALL" key followed by "7" to select "Other" and display the non MAF-
mapped zone alarms or faults (excludes "status only" zones).
5.9 BRIGADE TEST
5.9.1 FUNCTION
The Brigade Test function turns on the Brigade alarm relay (if programmed to) i.e.
signals alarm to the Brigade and turns on the "ALARM" LED. For a network system, the
brigade signalling may be at a remote panel in which case a command is sent across the
network to operate the alarm relay, but the local alarm LED will still turn on after "BRIG
TEST" key has been held for 2 seconds.
5.9.2 OPERATING SEQUENCE
Press and hold the "BRIG TEST" key for at least 2 seconds:
- The MAF alarm relay will activate (if programmed to).
- The "ALARM" LED will turn on, (if the relay is programmed to
operate).
Release the "BRIG TEST" key.
After a short period:
- The MAF alarm relay will de-activate and the "ALARM" LED
will turn off unless there are unisolated MAF mapped zones
still in alarm.
Note that the MAF alarm relay operation of the "BRIG TEST" key can be disabled via
system programming. If so disabled, pressing the "BRIG TEST" key will not result in an
alarm signal to the brigade, but the BGT token in the output logic will still become TRUE,
and an event will be logged to the history and printer.