F3200 Operator's Manual Document No: LT0119
Network Systems
Page 11-28 29 July 2002 Issue 2.04
Entering a Point Number
A point number is entered as three numeric values (SID.Responder.Point) with the
key being used to enter the separator. Press the ENTER key after entering 0, 1, 2 or 3
numeric values. If the ENTER key is pressed without entering any numeric values then
the first point on the first SID programmed in the local SID list will be recalled.
If a SID number is entered but no responder or point number, then the first point on that
SID will be recalled (even if the SID does not appear in the local SID list).
If a SID number and responder number are entered, but no point number, then the first
point on the selected responder will be recalled.
The name and number of the selected point will be shown on the display plus a menu of
options.
1: Status 2: Analogue Values 3: Analogue levels 4: %Dirty
Press numeric key 1, 2, 3 or 4 for the desired display or press NEXT or PREV keys to
step to the next or previous point.
When the status, analogue values, analogue levels or %Dirty of the point is/are being
displayed, the
key may be pressed to bring up the menu of:
1: Status 2: Analogue Values 3: Analogue levels 4: %Dirty
Alternatively, instead of pressing the RECALL key to bring up the menu, the numeric
keys 1 to 4 may be used to go directly to a particular display.
At any of the four status displays, the
OR
keys may be pressed to initiate reset or isolate/de-isolate commands. The NEXT or
PREV keys may be used to step to the next point.