Document No: LT0119 F3200 Operator's Manual
Network Systems
Issue 2.04 29 July 2002 Page 11-29
11.11.2 OFF-NORMAL POINT RECALL
Remote devices on the network may be searched for points with a particular off-normal
condition.
From the base display press:
A menu of options will then be shown. Press numeric key 1 to 6 to select as follows:
1. Status - this allows the status of a specific point to be displayed.
2. Off Normal - searches for points with any off-normal condition.
3. Alarms - searches for points in alarm.
4. Pre-Alarms - searches for points in pre-alarm.
5. Faults - searches for points in fault.
6. %Dirty – searches for points that have %Dirty greater than a percentage you will be
asked to enter.
7. More - this selects a second menu of options as follows:
1. Isolates - searches for isolated points.
2. Scan Fail - searches for scan failed points.
3. Maint Alerts - searches for points in maintenance alert.
4. Operated - searches for operated points.
6. More - selects the first menu again.
After the type of search has been selected a prompt is given for the
SID.Responder.point to start the search from. If no SID, responder nor point are entered
then the search will start with the first point on the first SID. If a SID number and no
responder/point numbers are entered, then the search starts with the first point on that
SID. If a SID number and responder number are entered, then the search starts with the
first point on that responder. If a SID, responder and point are all entered, then the
search starts at that point.
11.11.3 POINT ISOLATE, DE-ISOLATE OR RESET
From the base display press either:
OR
If the panel does not have a POINT key, then the RELAY key should be used.
Depending on the type of panel, either a menu of options will appear or the operator will
be immediately prompted to enter a point number. If a menu appears, select option 4:
Network Point and then enter a point number.