F3200 Operator's Manual Document No: LT0119
Operating Instructions - Zone Functions
Page 7-8 29 July 2002 Issue 2.04
OPERATING SEQUENCE (CONTINUED)
To reset a range of zones
:
From the base display, press:
The LCD will display the range of zones selected. Press the "ACK" key to initiate the
reset of zones nn to mm inclusive or press the "CLEAR ESC" key to abort with no reset.
7.3.3 NOTES
(a) Single digit zone numbers can be entered as "n" followed by "AND" or "RESET"
as appropriate, i.e. leading zeros are not required.
(b) If a detector or circuit is still in alarm or fault, then after the zone reset delay and
the circuit input delay the zone will return to alarm or fault.
(c) If the amber fault indicator reappears, then isolate the zone and call the service
company.