Document No: LT0119 F3200 Operator's Manual
Network Systems
Issue 2.04 29 July 2002 Page 11-5
11.3 LCD TOTALS, LEDs, OUTPUTS &
BUZZER OPERATION
For a networked F3200 or NDU, the interpretation of the front panel LEDs is described in
Section 4.1.1.
However, the operation of the Off-Normal totals, buzzer, MAF relays, and Ancillary relays
may be affected by states coming from other panels on the network, depending on
programming.
11.3.1 LCD TOTALS
The totals shown on the LCD display may include totals received from other devices on
the network.
A recall net SID status function is provided to show the individual totals local to this panel
and the totals currently being received from any other device on the network (from the
base display press RECALL RECALL 3 - refer to Section 11.6.2). Refer also to Section
4.2.2 (Base Display).
11.3.2 BUZZER OPERATION
The buzzer turns on:
Steady: For a local fault or system fault or a MAF fault, standby condition
or System fault from another network device for which this panel
has been programmed to include the totals of.
Pulsing: For a new alarm being put into the FFCIF list or a new MAF alarm
on the local panel.
Rapid Pulsing: For a local test failure, e.g. system test.
The buzzer is turned off:
1. Whenever a key is pressed on the keypad.
2. When there are no more unisolated alarms or faults.
3. When a system fault reset command is received from another device on the
network.