Document No: LT0119 F3200 Operator's Manual
Appendix A
Issue 2.04 29 July 2002 Page A-1
APPENDIX A
COMPATIBLE ACTUATING DEVICES (DETECTORS)
The following detectors are compatible with the F3200 System. The maximum number
of detectors per circuit is indicated by the columns 4mA and IS, for Standard and
Intrinsically Safe applications respectively. Refer to the F3200 Installation Manual
LT0122 for details on Intrinsically Safe installations.
DETECTORS CERTIFIED WITH F3200 FIP
MAX
NO.
TYPE DESCRIPTION BASE 4mA IS
MD614A HEAT DETECTOR TYPE A M614 40
-
MD614C HEAT DETECTOR TYPE C M614 40
-
MF614 IONISATION SMOKE DETECTOR M614 40
-
MR614 PHOTOELECTRIC SMOKE DETECTOR M614 40
-
MR614T PHOTOELECTRIC SMOKE DETECTOR M614 40*
1
-
MU614 CO FIRE DETECTOR M614 40
-
T614A HEAT DETECTOR TYPE A M614 40 -
T614B HEAT DETECTOR TYPE B M614 40 -
T614C HEAT DETECTOR TYPE C M614 40 -
T614D HEAT DETECTOR TYPE D M614 40 -
MF301Ex x IONISATION SMOKE DETECTOR M300 40
40
MR301Ex x PHOTOELECTRIC SMOKE DETECTOR M300 40
40
MR301TEx x PHOTOELECTRIC SMOKE DETECTOR M300 40
40
MS302Ex x INFRA-RED FLAME DETECTOR M300 40
40
S111 x INFRA-RED FLAME DETECTOR (IS) - 40 35
S121 x INFRA-RED FLAME DETECTOR (IS) - 40 35
S131 x INFRA-RED FLAME DETECTOR (IS) - 40 35
S231i+ x INFRA-RED FLAME DETECTOR (IS) - - 11
S231i+ INFRA-RED FLAME DETECTOR AND ZAU401 - 5 5
S231f+ INFRA-RED FLAME DETECTOR AND ZAU401 - 5 -
S261f+ INFRA-RED FLAME DETECTOR - 40 -
SU0600 15V MCP - 40 -
*
1
For ambient temp < 30°C. Max Qty is 34 otherwise
Table I MINERVA/THORN Detectors
DETECTORS CERTIFIED WITH F3200 FIP
MAX
NO.
TYPE DESCRIPTION 4mA
DCA-B-60R HEAT DETECTOR TYPE A 40
DCA-B-90R HEAT DETECTOR TYPE C 40
DCD-A HEAT DETECTOR TYPE A WITH YBO – R/4A BASE 40
DCD-C HEAT DETECTOR TYPE C WITH YBO – R/4A BASE 40
DFE-60B (DFB-60B) HEAT DETECTOR TYPE B 40
DFE-90D (DFB-90B) HEAT DETECTOR TYPE D 40
DFJ-60B HEAT DETECTOR TYPE B WITH YBO – R/4A BASE 40
DFJ-90D HEAT DETECTOR TYPE D WITH YBO – R/4A BASE 40
SIJ-ASN IONISATION SMOKE DETECTOR WITH YBO – R/4A BASE 40
SLR-AS PHOTOELECTRIC SMOKE DETECTOR WITH YBO – R/4A BASE 40
SIF-AM IONISATION SMOKE DETECTOR 40
SIH-AM IONISATION SMOKE DETECTOR 40
SLK-A PHOTOELECTRIC SMOKE DETECTOR 40
SLG-AM PHOTOELECTRIC SMOKE DETECTOR 40
HF-24A ULTRAVIOLET FLAME DETECTOR 18
WITH YBC-RL/4AH4, YBF-RL/4AH4 OR YBF-RL/4AH4M BASES
Table II HOCHIKI Detector Range