EasyManua.ls Logo

Tyco F3200 - Appendix A Compatible Actuating Devices (Detectors)

Tyco F3200
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Document No: LT0122 F3200 Installation & Programming Manual
Installation & Wiring
Issue 2.7 5 July 2001 Page 8-9
FIG 8.2.2
GOOSENECK CABLING
8.2.2 MAINS WIRING
The mains (240Vac) supply must be connected in accordance with AS1670.1 and AS3000
regulations.
Ensure the mains cables to the FIP are isolated at the
Distribution Board
before connecting to the FIP.
The mains cable connects to the 3 way terminal block mounted to the cabinet rear behind
the mains cover.
(a) Remove the mains cover with a Pozi screw-driver.
(b) Shape the mains cable to fit through the grommet in the slot in the top of the cover,
cut to length and strip only 20mm of the PVC cable sheath.
(c) Connect the wires: blue (black) to N
brown (red) to A
green/yellow (green) to E
Take care when stripping not to "nick" wires.
(d) Cable tie the cable to the cabinet.
(e) Refit the mains cover .

Table of Contents

Other manuals for Tyco F3200

Related product manuals