Document No: LT0122 F3200 Installation & Programming Manual
Installation & Wiring
Issue 2.7 5 July 2001 Page 8-13
W A R N I N G
Apart from the mains supply to the FIP only ELV wiring may enter the cabinet.
Relays must not be used to directly switch medium
or high voltage.
+VNBF o─────┐
┌─ SUPERVISION RETURN
| SUP o─────┼─────────┬───────────────────────────────────────┐
|
ANCIL| NC o─────┘ <- ALTERNATIVE
1 |
| COM o───────┬───────┴───┬───────────┬───────────┬───────────┤
└─
╒╧╕ ┌┴┐ ┌┴┐ ┌┴┐ ┌┴┐
│1N4004 └┬┘ └┬┘ └┬┘ └┬┘
└┬┘
0V o───────┴───────────┴───────────┴───────────┴───────────┘
SUPPRESSION DOOR HOLDERS
DIODE
A. WITH SUPERVISION OF LOOP POSITIVE WIRING ONLY
+VNBF o─────┐
┌─ SUPERVISION RETURN
| SUP o─────┼───────────────────────────────────────────┐
|
ANCIL| NC o─────┘
1 |
| COM o───────┬───────┬───────┬───────┬─────┬─────┬───┐
└─
╒╧╕ ┌┴┐ ┌┴┐ ┌┴┐ ╒╧╕ ┌─┴─┐ o NO
* └┬┘ └┬┘ └┬┘ * /
└┬┘ └┬┘ └─┬─┘ o COM
0V o───────┴───────┴───────┴───────┴─────┴─────┘ └─┘
* SUPPRESSION DOOR HOLDERS +24V RELAY
DIODE
B. WITH SUPERVISION OF LOOP POSITIVE AND NEGATIVE WIRING
FIG 8.4.1
EXAMPLE OF DOOR HOLDER WIRING WITH SUPERVISION