Document No: LT0122 F3200 Installation & Programming Manual
Installation & Wiring
Issue 2.7 5 July 2001 Page 8-17
FIG 8.5.2
EXAMPLE OF MULTIPLE MINI-GENS WITH 3 BRANCHES OF SPEAKERS
Note that this configuration requires that the relay confirmation (ACT) be disabled, which
requires V2.09 or greater software.
FIG 8.5.3
EXAMPLE OF A SUPERVISED EVAC CCT USING 2 POLES OF AN 8RM RELAY
F3200
+
24V
Mini-Gen
(PA0895)
-
+
-
+
-
S
+
-
+
-
S
+
-
FIRE PANEL
DC IN
DC IN
LINE
OUT
LINE
OUT
2-W LINK
FITTED
2-W LINK
FITTED
24V
Mini-Gen
(PA0895)
Bells +
Bells -
EOLR
10k 2W
EOLR
10k 2W
EOLR
10k 2W
+VBF
NO
Pole 2 NC
C
Pole 1 NO
NC
C
S
0V
4K7 EOLR
(27k for dual
branch)