Document No: LT0122 F3200 Installation & Programming Manual
Appendix A
Issue 2.7 5 July 2001 Page A-3
BASES COMPATIBLE WITH DETECTORS
DET/
BASE
Z51B Z52B Z54B
&
Z54B
MK2
Z55B Z56 Z56N Z500 Z500
N
Z91C
&
Z94C
Z94
&
MH2
C24B
&
X
&
X
&&
C29B
&
X
&
X
&& '
C29B
Ex
XX
&
P24B
&
X
&
X
&&
P29B
&
X
&
X
&&
T56B
&&&&&&&&
Table IV
Grinnell Detector/Base Range
&
These detector/base combinations are compatible.
X These detector base combinations have been used in the past, however they are
technically incorrect (see Product Bulletin PBD0004).
' The combination of Z94 base and MH2 heater unit is not SSL approved.
Note that Z52, Z55, Z56N and Z500N are non-electronic bases (ie. non-latching, non-
indicating) and do not add any extra voltage to the detector in alarm (eg. if a T56B heat
detector is used with these, it shorts directly across the AZC).
╔═════════════════════════════════════════════════════════╤═══════╗
DETECTORS COMPATIBLE WITH F3200 FIP MAX NO.
╟─────────┬───────────────────────────────────────────────┼───────╢
TYPE DESCRIPTION 4mA
╠═════════╪═══════════════════════════════════════════════╪═══════╣
DCD-A (DCC-A & DCA-B-60R) HEAT DETECTOR TYPE A 40
╟─────────┼───────────────────────────────────────────────┼───────╢
DCD-C (DCC-C & DCA-B-90R) HEAT DETECTOR TYPE C 40
╟─────────┼───────────────────────────────────────────────┼───────╢
DFJ-60B (DFE-60B & DFB-60B) HEAT DETECTOR TYPE B 40
╟─────────┼───────────────────────────────────────────────┼───────╢
DFJ-90D (DFE-90D & DFB-90D) HEAT DETECTOR TYPE D 40
╟─────────┼───────────────────────────────────────────────┼───────╢
SIJ-ASN (SIH-AM & SIF-A)IONISATION SMOKE DETECTOR 40
╟─────────┼───────────────────────────────────────────────┼───────╢
SLR-AS (SLK-A & SLG-AM) PHOTOELECTRIC SMOKE DETECTOR 40
╟─────────┼───────────────────────────────────────────────┼───────╢
HF-24A ULTRAVIOLET FLAME DETECTOR 18
╟─────────┴───────────────────────────────────────────────┴───────╢
ALL WITH YBC-RL/4AH4, YBF-RL/4AH4 OR YBF-RL/4AH4M OR YBO-R/4A