Document No: LT0122 F3200 Installation & Programming Manual
System Specifications
Issue 2.7 5 July 2001 Page 3-11
ICL+R = Current sourced through current limit and pull up resistor
IAV = Current available to detectors with EOLR fitted
IAV = ICL+R - IEOLR
GRAPH 3.4.3
AZC CURRENT VS VOLTAGE MODE 2 (HIGH CURRENT)
A short circuit at the end of an 800 Ohm line will give a B2 (Detector Operated) alarm.
A short circuit at the end of a 2k Ohm line will give a B3 (programmable) condition.
GRAPH 3.4.4
ACZ CURRENT VS VOLTAGE MODES 3 & 4 (LOW CURRENT & TAMPER)