Document No: LT0122 F3200 Installation & Programming Manual
System Specifications
Issue 2.7 5 July 2001 Page 3-17
MAF/PSU OUTPUTS (CONTINUED)
Non-Battery Backed DC Supply
Rating 28Vdc nom
2Adc, fused
+VNBF
Termination 1 non-demountable screw terminal
4sq mm max cable
1 demountable screw terminal
1.5sq mm max cable
RZDU Comms
Tx, Rx, 0V 3 Wire (+VBF2 also available)
Transmission Rate 1200 Baud
Protocol Vigilant F4000
Termination Demountable screw terminals
1.5sq mm max cable
3.5.4 CONTROLLER/DISPLAY OUTPUTS
Spare Parallel Outputs
(not fitted)
Number 6
Type CMOS
Voltage Rating 0-5V
Termination 10 Way FRC pcb header, J10
Serial I/O
Printer/Programmer Port
Form Pseudo RS232
Rx, Tx, 0V signals only
Transient Protection Allows external wiring
Transmission Rate 9600 Baud
Protocol ASCII Xon, Xoff
Termination 4 Way .156" male molex (J1)
9 Way Miniature D available via transition cable
Part number LM0041
Female Pins (socket)

Table of Contents