Model RM-1 
Riser Manifold 
Commercial and Residential
Page 1 of 8  AUGUST 2021  TFP963
Worldwide 
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet 
TFP2300 for warnings pertaining to 
regulatory and health information.
General 
Description
The TYCO commercial and residential 
Model RM-1 Riser Manifold provide 
the necessary waterflow alarm, pres-
sure gauge, alarm test orifice, drain, 
and sight glass equipment in a single 
assembly for use in NFPA 13 com-
mercial sprinkler systems and in NFPA 
13D/13R residential sprinkler systems 
as follows:
NFPA 13*
•  1-1/2 in. (DN40)
Male Thread x Female Thread
•  2  in.– 6  in.  (DN50 – DN150)
Groove x Groove
NFPA 13D
•  1 in. (DN25)
Female Thread x Female Thread
NFPA 13R
•  1-1/2 in. (DN40)
Male Thread x Female Thread
•  2 in. (DN50)
Groove x Groove
* Although the Riser Manifold described in this techni-
cal data sheet is intended for NFPA 13 sprinkler sys-
tems, it may be used for NFPA 13D or 13R residential 
sprinkler systems, where a test orice of 2.8K or 4.2K  
is acceptable.
The variety of sizes and grooved end 
connections allow cost effective and 
easy transition to check valves, control 
valves, and system piping. The Model 
RM-1 Riser Manifolds may be installed 
either horizontally (flow switch on top) 
or vertically (flow going up) orientation, 
for both single sprinkler rises and floor 
control in high-rises.
Optional Pressure Relief Kits feature a 
175 psi pressure relief valve and trim 
components for convenient integration 
into commercial and residential riser 
manifold assemblies.
The pressure relief valve, installed in 
manifold assemblies above the nor-
mally closed test and drain or drain 
valve, automatically bleeds system 
pressure exceeding 175 psi through a 
flexible hose connected to the mani-
fold drain outlet (Ref. Figure 5), reduc-
ing system pressure to 175 psi.
NOTICE
The Model RM-1 Riser Manifolds 
described herein must be installed 
and maintained in compliance with this 
document, as well as with the applica-
ble standards of the NATIONAL FIRE 
PROTECTION ASSOCIATION (NFPA), 
in addition to the standards of any other 
authorities having jurisdiction. Failure 
to do so may impair the performance 
of these devices.
The owner is responsible for main-
taining their fire protection system 
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any 
questions.
Technical 
Data
Approvals
UL and ULC Listed
FM Approved
Listed by California State Fire Marshall
Maximum Working Pressure
300 psi (20,7 bar)
Friction Loss
See Table A
Test Orifice
1 in.– 3  in.  (DN25 – DN80)  Manifolds:  2.8K 
4 in.– 6  in.  (DN100 – DN150)  Manifolds:  4.2K
Finish
Red Painted