EasyManua.ls Logo

UNI-T UT241 - Page 19

UNI-T UT241
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33 34
7.8 Phase Sequence Detection
1 As shown in Figure 14, press MENU to select gear of voltage (V)+voltage (V)+voltage
(V) . Insert red testing pen into V1 jack, blue testing pen into V2 jack, yellow
testing pen into V3 jack and black testing pen into COM jack and connect 4
testing pens to measured power, three-phase load and grounding end.
Figure 14
1 As shown in Figure 15, 16 &17, instrument will display phase sequence detection result for
load loop of three-phase four-wire system.
Figure 15 Any phase of voltage
is less than 30V.
Figure 16 Inverted sequence Figure 17 Positive sequence
2 Positive sequence layout is shown in following figure. As shown in Figure 18, LCD can
display positive sequence detection result when connecting V1, V 2 and V3 jacks t o
Phase A, B & C if three-phase voltage exceeds 50V.
Positive
sequence
Figure 18
UT241/242/243 OPERATING MANUALUT241/242/243 OPERATING MANUAL