10
The heads and delivery pipe of the compressor are normally quite hot.
Be careful when working near the condensing coils.
The aluminium fins are very sharp and can cause serious injuries.
After the maintenance operations, close the panels by fixing them with screws.
6.2 LIFTING AND HANDLING
During unloading and positioning of the unit, utmost care must
be taken to avoid abrupt or violent manoeuvres in order to
protect the internal electronic components. The units can be
lifted by means of a forklift or, in alternative, with belts, being
sure no
t to damage the side panels and the cover. It is
important to keep the unit horizontal during these operations.
6.3 POSITIONING AND MINIMUM TECHNICAL CLEARANCES
All models of the HP_OWER ONE range are designed and constructed for outdoor installations.
It is advisable to create an adequately sized support base for the unit. The units transmit a small amount of vibrations to the
ground: it is nonetheless advisable to apply vibration dampers between the base frame and support surface. It is very important to
avoid recirculation between intake and delivery air, so as not to downgrade performance of the unit or even to interrupt its
normal operation.
At least 5 m from the appliance there must be no shafts or manholes where gases might build up and generate an
explosive atmosphere.
This is why the Minimum clearances shown below must be strictly guaranteed.
Do not obstruct or cover the vents on the top cover.