21
Power supply Input
1-Ph/N/PE, 230Vac, 50Hz
Connect the neutral cable from the mains
Connect the phase cable from the mains
Power supply Input
3-Ph/N/PE, 400 Vac, 50Hz.
(only for HP_OWER ONE 160RT/RTK,
HP_OWER ONE 180RT/RTK)
Connect the neutral cable from the mains
Connect the phase cable L1 from the mains
Connect the phase cable L2 from the mains
Connect the phase cable L3 from the mains
Modbus RTU+ signal connection for remote control panel (R+)
Modbus communication
Modbus RTU- signal connection for remote control panel (R-)
X-4.1
Connection of modbus RTU earth reference for remote control
panel (GNDR)
Remote Control Panel power supply (12V, 50Hz, 500mA)
Output for power supply 12Vac, 50Hz
Remote Control Panel power supply (12V, 50Hz, 500mA)
X-17.1/X-17.2
Domestic hot water temperature probe / thermostat digital
input
Analog (10KΩ NTC sensor at 25 ° C β
34-35) or digital input
X-19.1/19.2 Plant’s remote temperature probe / thermostat digital input
Analog input (10KΩ NTC sensor at 25 °
C β 34-35) or digital input
Double set point / domestic hot water digital input
0-10V (+) signal input to modify set point
Analogue input (ST10)
0-10V (-) signal input to modify set point
X-6.1/X-6.2 Plant’s electric heater
Under-voltage output single phase
230Vac, 50Hz, 2A resistive,
X-9.1/X-9.2
Exchanger heater (only in the version -K) / Available resource (in
models without antifreeze kit)
Under-voltage output single phase
230Vac, 50Hz, 2A resistive
X-10.1/X-10.2
Base heater (only in the version -K) / Available resource (in
models without antifreeze kit)
Under-voltage output single phase
230Vac, 50Hz, 2A resistive.
X-11.1/X-11.2 Domestic hot water valve output
Output 1- phase 230Vac, 50Hz, 2A
resistives.
X-14.1/X-14.2 Double set-point valve output
Output 1- phase 230Vac, 50Hz, 2A
resistives.
X-16.1/X16.2
Summer/winter mode change input from remote (to activate the
function, see the relevant paragraph in the User interface
Voltage-free digital input
X-15.1/X15.2
Remote on/off input
(closed=machine on / open=machine off)
Voltage-free digital input
7 STARTUP
Before start-up:
• Check that the diagrams and manuals of the installed machine are available.
• Check that the wiring and plumbing diagrams of the plant the machine is connected to are available.
• Check that the shut-off valves of the water circuits are open.
• Check that the water circuit was filled under pressure and the air vented.
• Check that all the plumbing connections are installed correctly and that all the indications on the rating plates are complied
with.
• Make sure that measures have been taken to discharge condensate.
• Check the electrical connection and correct fastening of all the terminals.
• Check that the electrical connections have been made according to standards in force, including earthing.
• Voltage must match that on the unit’s rating plate.
• Make sure that the electric voltage is within the tolerance limits (±10%).
• Check that the electric heaters of the compressors are properly powered.
• Check that there are no gas leaks.
• Before switching the unit on, check that all panels are positioned correctly and well-fixed with screws.
Fill in the "First start request" form in the document envelope.