28
Measurement
Completed
Notes
8
Repairs on sealed connectors
During operations on sealed components, completely isolate the
device from the power supply, before removing the sealed covers.
If, during operations, the power supply is absolutely necessary:
Position a continuously operating refrigerant detector in the most
critical places, so that it emits a warning signal in case of potentially
dangerous situations.
Pay particular attention that any operation on the electrical
components does not entail changes to the connectors which could
influence their protective properties. These include damage to the
feet; too many connections to a single terminal; connections that
do not correspond to the manufacturer's specifications; damage to
seals; and incorrect installation of the cable entries.
Make sure the device is installed correctly.
Verify that the seals are secured in place. Check to make sure that
the seals effectively prevent the entry of a flammable atmosphere.
Replace defective seals
Please note that
Used as a sealant, silicone can affect
on devices for detecting leaks.
Do not use silicone as a sealant.
Spare parts must comply with the manufacturer's specifications.
Work on components suitable for flammable atmospheres: It is
not imperative that these components are isolated from the power
supply.
9
Repair operations on components suitable for flammable atmospheres
Do not connect any capacitive or continuous inductive loads to the
device unless you have made sure not to exceed the all
owable voltage
and current.
In areas with flammable atmospheres, apply voltage only to
components suitable for fl
ammable atmospheres.
Use only original or approved parts. In the event of a leak, the use of
other parts may result in the ignition of the
refrigerant.
10
Wiring
Check that the electrical connection is not subject to wear, corrosion,
tension, vibrat
ion, sharp edges or other unfavorable environmental
conditions.
When checking, also take into account the effects of time and
continuous vibrati
ons on the compressor and fans.
11
Refrigerant detectors
Do not, for any reason, use possible sources of ignition to detect
any leaks or leaks of refrigerant.
Leak detection lamps or other open flame detectors must not be
used.