There are five rules for the refrigerant tubing related to length and height between components.
#1: (Height) The highest indoor unit must be less than 32 ft above the outdoor unit.
#2: (Height) The lowest indoor unit must be less than 32 ft. below the outdoor unit.
#3: (Height) The highest indoor unit must be less than 19 ft. above the lowest indoor unit.
#4: (Length) The longest distance from any indoor unit to the outdoor unit must be less than L1, L2, L3, L4.
#5: (Length) The sum total of distance of each indoor unit to the outdoor unit must be less than Ltot.
IL00533a.CVX
L Tot. = Total length of all line sets (L1 + L2 + L3...)
Maximum line length allowed
* REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT (R-410A)
For 1/4" x 3/8" line set = 0.16 oz/ft (15g/m)
For 1/4" x 1/2" line set = 0.22 oz/ft (20g/m)
Example: IS18G050 as single-split with 1/4 x 3/8 line set of 60 ft, The excess line length is 35 ft. So add 35x0.16= 5.6 oz.
R-410A.
No additional charge of compressor oil is necessary.
WITH ADDITIONAL REFRIGERANT*