Unidrive M200 /M201 Quick Start Guide 1
Issue Number: 1
This guide is intended to provide basic information required in order to set-up a drive to run a motor.
Please refer to the Unidrive M200 / M201 User Guide which is available to download from
www.controltechniques.com/userguides.
1 Safety information
2 Product information
2.1 Ratings
Unidrive M200, M201
Quick Start Guide
This guide does not include safety information. Incorrect installation or operation of the
drive, could cause personnel injury or equipment damage. For essential safety
information, please refer to the Unidrive M200 / M201 User Guide or the safety booklet
supplied with the drive.
Model
Input
phases
Max.
cont
input
current
Max input
fuse rating
Nominal cable size
Output current
European USA
1 Ph 3 Ph Input Output Input Output
Max.
cont
output
current
Nominal
power
Motor
power
ph A A A
mm
2
mm
2
AWG AWG A kW hp
01100017 1 10 1 1 16 16 1.7 0.25 0.33
01100024 1 16
1 1 14 16 2.4 0.37 0.5
01200017 1 6
1 1 16 16 1.7 0.25 0.33
01200024 1 6
1 1 16 16 2.4 0.37 0.5
01200033 1 10
1 1 16 16 3.3 0.55 0.75
01200042 1 16
1 1 16 16 4.2 0.75 1
02100042 1 18.8 20
2.5 1 12 16 4.2 0.75 1
02100056 1 24 25
4 1 10 16 5.6 1.1 1.5
02200024 1 / 3 5.3/4.1 6 6 1 1 16 16 2.4 0.37 0.5
02200033 1 / 3 8.3/6.7 10 10 1 1 16 16 3.3 0.55 0.75
02200042 1 / 3 10.4/7.5 16 10 1 1 16 16 4.2 0.75 1
02200056 1 / 3 14.9/11.3 20 15 2.5/1.5 1 12/14 16 5.6 1.1 1.5
02200075 1 / 3 18.1/13.5 20 15 2.5 1 12 16 7.5 1.5 2
02400013 3 2.4
6 1 1 16 16 1.3 0.37 0.5
02400018 3 2.9
6 1 1 16 16 1.8 0.55 0.75
02400023 3 3.5
61 116162.30.751
02400032 3 5.1
61 116163.21.11.5
02400041 3 6.2
10 1 1 16 16 4.1 1.5 2
03200100 1 / 3 23.9/17.7 25 20 4 1.5 10/12 14 10 2.2 3
03400056 3 8.7
10 1 1 14 16 5.6 2.2 3
03400073 3 12.2
16 1.5 1 12 16 7.3 3 3
03400094 3 14.8
16 2.5 1.5 12 14 9.4 4 5
04200133 1 / 3 25 20 4/2.5 2.5 10 12 13.3 3 3
04200176 3
25 4 2.5 10 12 17.6 4 5
04400135 3
20 2.5 2.5 10 12 13.5 5.5 7.5
04400170 3
25 4 2.5 10 12 17 7.5 10
The nominal cable sizes shown in the table above, are provided as a guide only. Ensure
that the cables used conform to the local wiring regulations.