Table 23. Drive suitability table for 500 V AC and 690 V AC liquid-cooled drives
2.3.3 Installation
The sine filter connection is shown in Figure 9 on page 22.
NOTE! The maximum motor cable length for the sine filter is 300 m. If a longer cable is used, it is
recommended to select one current class higher sine-filter type to prevent overheating.
NOTE! Cooling of the sine filters is based on natural air convection (AN). Therefore a proper
ventilation and placement inside the enclosure must be ensured during assembly. Suitability for
base or wall mounting is shown in Table 26.
500 V AC drive Filter, IP00 class 500 V AC drive
Filter, IP 54
class
690 V AC drive Filter, IP00 class
NX_0016 5 SIN-0018-5-0-P NX_0016 5 SIN-0016-5-5-P NX_0170 6 SIN-0185-6-0-P
NX_0022-0031 5 SIN-0032-5-0-P NX_0022 5 SIN-0023-5-5-P NX_0208-0261 6 SIN-0287-6-0-P
NX_0038-0045 5 SIN-0048-5-0-P NX_0031 5 SIN-0032-5-5-P NX_0325-0385 6 SIN-0390-6-0-P
NX_0061-0072 5 SIN-0075-5-0-P NX_0038 5 SIN-0038-5-5-P NX_0416-0460 6 SIN-0460-6-0-P
NX_0087-00105 5 SIN-0110-5-0-P NX_0045 5 SIN-0046-5-5-P NX_0502-0590 6 SIN-0620-6-0-P
NX_0140-0168 5 SIN-0180-5-0-P NX_0061 5 SIN-0061-5-5-P NX_0650-0750 6 SIN-0780-6-0-P
NX_0205-0261 5 SIN-0270-5-0-P NX_0072 5 SIN-0072-5-5-P NX_0820-0920 6 SIN-0920-6-0-P
NX_0300-0385 5 SIN-0410-5-0-P
- -
NX_1030-1180 6 SIN-1180-6-0-P
NX_0460-0590 5 SIN-0600-5-0-P
- -
NX_1300-1500 6 2xSIN-0780-6-0-P
NX_0650-0820 5 SIN-0840-5-0-P
- -
NX_1700-2340 6 2xSIN-1180-6-0-P
NX_0920-1150 5 SIN-1160-5-0-P
- -
NX_2700-3100 6 4xSIN-0920-6-0-P
NX_1370 5 SIN-1480-5-0-P
- - - -
NX_1640 5 2xSIN-0840-5-0-P
- - - -
NX_2060 5 2xSIN-1160-5-0-P
- - - -
NX_2300-2470 5 2xSIN-1480-5-0-P
- - - -
NX_2950 5 4xSIN-0840-5-0-P
- - - -
NX_3710-4140 5 4xSIN-1160-5-0-P
- - - -