25
Pipe Marking
In accordance with AS/NZS 3500.1:2003,
pipe and outlets connected to the Vada Digital
Water Switching Unit must be marked as
follows:
Outlets connected to the unit must be
marked with the wording “RAINWATER”.
Piping systems connected the unit must
be clearly marked at 1m spacings with the
word “RAINWATER”.
8. Install a pump cover to protect your set up
from wind, rain, and sun.
PART 8: CONNECT
TO A POWER SUPPLY
1. Check that the powerpoint is located
in a dry and flood free location.
2. Ensure the power supply cord is supported
by the delivery pipes at 3 metre intervals.
3. Ensure there are no water traces on the
pump connectors. Push them firmly into
each other to ensure intended splash
(water) proof protection.
3 metres