IMPORTANT: If failure appears, power supply must be switched off and only then performed fault
eliminaon works.
Descripon of operang EKA NV … PTC/2NTC*
Electrical duct heaters EKA NV … PTC/2NTC are designed with integrated temperature control, PTC (air
velocity) and two temperature sensors, potenometer on the top of the heater casing for temperature setpoint.
When the heater power supply is switched on, controller (EKR-K) is in preparaon mode for 30 seconds, LED 1
flashes once every 5 seconds. If air velocity is detected by PTC sensor (rapid LED 1 flashes when Min. 1,5 m/s is
detected) aer preparaon mode ends, LED 1 will start to flash once every second and controller will iniate the
heang based on demand, LED 2 is indicang when heang is iniated. If there is no air velocity detected, controller
will not iniate the heang unl air velocity detected.
Heaters EKA NV … PTC/2NTC can operate in two modes:
1. Control by the supply air temperature sensor (TJ-K10K), when the first (1) switch of JP1 -(R37) (see Fig. 1 on
page 4) is in posion OFF. LED 1 flashes once per second. Setpoint temperature (0…30) °C.
2. Control by the supply (TJ-K10K) and by the room (NTC10) air temperature sensor, when the first (1) switch of
JP1 -(R37) (see Fig. 1 on page 4) is in posion ON. LED 1 flashes twice per second. Setpoint temperature (15…30) °C.
In this mode is preprogrammed the minimum (15°C) and the maximum (40°C) temperatures of supply air. The room
air temperature sensor is mounted in the wired panel TR NTC10.
Depending on the operang mode there can be set the different desired (setpoint) air temperature by
potenometer on the top of the heater casing.
* - non standart opon. Fore more informaon please contact sales@ventmaka.lt
2. Control by the supply (TJ-K10K) and by the room (NTC10) air temperature sensor, when the first (1) switch of
JP1 -(R37) (see Fig. 1 on page 4) is in posion OFF. LED 6 flashes once per second. Setpoint temperature (15…30) °C.
In this mode is preprogrammed the minimum (15°C) and the maximum (45°C) temperatures of supply air. The room
air temperature sensor is mounted in the wired remote control panel TR5K NTC10.
Depending on the operang mode there can be set the different desired (setpoint) air temperature by wired
remote control panel TR5K NTC10.
* - non standart opon. Fore more informaon please contact sales@ventmaka.lt
IMPORTANT: If failure appears, power supply must be switched off and only then performed fault
eliminaon works.
Electrical duct heaters EKA NI … PTC/2NTC are designed with integrated temperature control, PTC (air velocity)
and two temperature sensors, wired remote control panel (TR5K NTC10) for temperature setpoint.
When the heater power supply is switched on, controller (EKR-K…) is in preparaon mode for 30 seconds, LED
1 flashes once every 5 seconds. If air velocity is detected by PTC sensor (rapid LED 1 flashes when Min. 1,5 m/s is
detected) aer preparaon mode ends, LED 1 will start to flash once every second and controller will iniate the
heang based on demand, LED 2 is indicang when heang is iniated. If there is no air velocity detected, controller
will not iniate the heang unl air velocity detected.
Heaters EKA NI … PTC/2NTC can operate in two modes:
1. Control by the supply air temperature sensor (TJ-K10K), when the first (1) switch of JP1 -(R37) (see Fig. 1 on
page 4) is in posion OFF. LED 1 flashes once per second. Set point temperature (0…30) °C.
2. Control by the supply (TJ-K10K) and by the room (NTC10) air temperature sensor, when the first (1) switch of
JP1 -(R37) (see Fig. 1 on page 4) is in posion ON. LED 1 flashes twice per second. Setpoint temperature (15…30) °C.
In this mode is preprogrammed the minimum (15°C) and the maximum (40°C) temperatures of supply air. The room
air temperature sensor is mounted in the wired remote control panel TR5K NTC10.
Depending on the operang mode there can be set the different desired (setpoint) air temperature by wired
remote control panel TR5K NTC10.
Descripon of operang EKA NI … PTC/2NTC*