FAI Set up
Installation
Normally Closed Input
A normally closed re alarm input from an FACP
should be wired across FAI- and FAI_P. A jumper
wire must be connected across FAI+ and FAI_P.
When the contact is open, this activates the FAI
in the AC62 which disables 12V/24V power to all
16 relay outputs.
Normally Open Input
A normally open re alarm input from an FACP
should be wired across FAI+ and FAI-. When the
contact is closed, this activates the FAI in the
AC62 which disables 12V/24V power to all 16
relay outputs.