Low limit of span or range. Set the low limit lower than
the lowest expected SV and PV display.
Full range
0
High limit of span or range. Set the high limit higher than
highest expected SV and PV display.
Full range
1000
Software filter.
0.00-100.0 5.0
Alarm 1 function. Refer to alarm function section for
detail.
nonE, Hi, Lo, dif.H,dif.L,
bd.Hi , bd.Lo, t.on,
t.oFF
Alarm 1 mode. Refer to alarm mode section for detail.
nonE, Stdy,
Lath, St.La
HH.mm, mm.SS
Alarm 2 function. Refer to alarm function section for
detail
nonE, Hi, Lo, dif.H,dif.L,
bd.Hi , bd.Lo, t.on,
t.oFF
Alarm 2 mode. Refer to alarm mode section for detail.
nonE, Stdy,
Lath, St.La
HH.mm, mm.SS
Alarm 3 function. Refer to alarm function section for
detail
nonE, Hi, Lo, dif.H,dif.L,
bd.Hi , bd.Lo, t.on,
t.oFF
Alarm 3 mode. Refer to alarm mode section for detail.
nonE, Stdy,
Lath, St.La
HH.mm, mm.SS
RS485 address 0-255 0
Communication baud rate. 2.4k=2400bps, 4.8k=4800 bps,
9.6k=9600 bps, 19.2k=19200 bps
2.4k, 4.8k,
9.6k, 19.2k
9.6k
Scaling for Linear Input
1.
Press the SET and DOWN keys simultaneously for 5 seconds to access “LnLo” parameter.
2. Adjust “LnLo” setting to correspond the low scale and after adjustment press
key once to
access “LnHi”
parameter.
3.
Adjust “LnHi” setting to correspond the high scale
and after adjustment press
key once for normal
operation.
Code Description Range Default
Low Scale of PT100 Not adjustable 0.0
High Scale of PT100
Not adjustable 800.0
Low Scale of Linear Input
-1999~9999(-199.9~999.9)
0.0
High Scale of Linear Input
-1999~9999(-199.9~999.9)
100.0