EasyManua.ls Logo

Vertiv DELTA 600 - Page 4

Vertiv DELTA 600
6 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DELTA 600
Battery charger / DC Power Supply
©2017 Vertiv Co. All rights reserved | DELTA 600 | 6012928 | Notice utilisation | v05 | 05.17
Adjusting the voltage U with the external potentiometer
The output voltage can be adjusted using the external potentiometer (use only the VERTIV potentiometer, code:
6002928). Connect the potentiometer as shown in the diagram. Set switches 2 and 3 to the "Us Manual" and
"External U" position. Setting range: see § Specifications.
Protections
The DELTA module is equipped with internal devices to protect both itself and the connected equipment:
Polarity inversion protection (Caution, the rating of fuses FB and FU, indicated in the specifications
table, must be respected).
Overload and output short-circuit protection by current limitation.
Fire protection in case of internal failure by input fuse.
Output overvoltage protection (Charger max.): protects the load in case of control loss by stopping the
module. Threshold set at the current voltage (floating or boost) + 10% of the rated voltage, and delayed
approximately 13 seconds (memorized fault).
No current measurement protection: protects the battery in case of loss of limitation by stopping the
module, 10 s delay (memorized fault).
End of battery discharge alarm (battery min.): Threshold set at 85% of the rated voltage, and delayed
2 seconds (fault not memorized).
These last faults are reported onto an NO + NC dry contact on terminals 1-2-3 of the connector, at rest in
default.
Note: To clear the memorized faults, power to the module must be turned off (mains and battery) for at least
30 seconds.
Fault report configuration:
The fault report may be configured in mM or D mode. The table below indicates the faults reported for each
mode.
mM
D
Charger max.
Battery min.
Battery test failure
No current measurement
Mains outage
Charger max.
Battery min.
Battery test failure
No current measurement
The following is recommended to avoid signal disruption:
do not use more than 2 meters of cable to connect auxiliaries,
do not route auxiliary wiring outside the cabinet in which the DELTA charger is installed,
route auxiliary wiring and power wiring separately,
twist the auxiliary connecting wires serving the same function.
CAUTION!
External U
2.275V/CELL
Us Manual
2.23V/CELL
mM
D
Us Auto
Internal U
1
2
4
3

Related product manuals