Liebert® MC™
60-Hz Air-cooled MicrochannelCondenser
-Premium/EC Fan
Installer/User Guide

Table of Contents

Other manuals for Vertiv Liebert MCL055

Questions and Answers

  • S
    sandovalwilliamAug 5, 2025
    How to troubleshoot Vertiv Liebert MCL055 Heat Pump condenser that will not start?
    • A
      Aaron LaraAug 5, 2025
      If the Vertiv Heat Pump condenser won't start, first check the voltage at the input terminal block to ensure there is power. If power is present, check if the circuit breaker or fuse for the low voltage transformer in the condenser has tripped; if so, locate and repair the problem within the condenser's electrical panel. Finally, verify that there is a low voltage signal to or from the indoor unit; if not, locate and repair any open circuits.
  • A
    Angela BowenAug 8, 2025
    What to do if SPD green and red LEDs are extinguished on Vertiv Heat Pump?
    • R
      Renee JohnstonAug 8, 2025
      If the green and red LEDs on your Vertiv Heat Pump's SPD are extinguished, begin by checking the voltage at the input terminal block to ensure proper voltage and phasing at the condenser. Next, inspect the electrical connections to the SPD for any faults and repair them. Finally, ensure that the condenser disconnect switch is in the On position and recheck the lights.
  • R
    Ryan DuranAug 13, 2025
    Why is there high discharge pressure in my Vertiv Liebert MCL055 Heat Pump?
    • S
      scottwilliamsAug 13, 2025
      High discharge pressure in your Vertiv Heat Pump can be caused by several factors. Begin by cleaning the condenser coil fins. Also, check if the condenser fans are operating and verify the low voltage signal from the indoor unit and check the fan motors and fuses. Finally, check the refrigerant charge, as a high charge can also cause this issue.
  • A
    Alicia HallAug 18, 2025
    What to do if Vertiv Liebert MCL055 Control Board LEDs do not light?
    • K
      Karen JohnsonAug 18, 2025
      If the control board LEDs on your Vertiv Heat Pump do not light up, check the connection to P24 to ensure it is securely connected. Also, check the connector from the transformer for loose terminals. Verify that the fuses next to P24 have not blown, and replace them if needed. Use a voltmeter to confirm that the output from the transformer is 24Vac ±10%, ensuring the correct primary leads are used. If there is no output voltage, verify that the primary connections are secure and receiving the correct voltage. If they are, replace the transformer.
  • J
    jasondavisAug 22, 2025
    What does it mean if SPD red LED is illuminated on Vertiv Liebert MCL055 Heat Pump?
    • N
      Nancy RobbinsAug 22, 2025
      If the red LED is illuminated on the SPD of your Vertiv Heat Pump, it indicates that a surge exceeding the SPD's rating has occurred. Replace the SPD and inspect other components for damage, replacing them as necessary.
  • R
    Robert QuinnAug 26, 2025
    Why Vertiv Liebert MCL055 Heat Pump fan will not run?
    • N
      Nicholas JeffersonAug 27, 2025
      If the fan on your Vertiv Heat Pump will not run, ensure that a jumper is installed between 24V and DIN1, specifically for Ziehl-Abegg fan motors. Install the jumper if it is missing.
  • D
    Deanna GrantAug 30, 2025
    What causes low discharge pressure in Vertiv Liebert MCL055 Heat Pump?
    • M
      Melissa DanielsAug 30, 2025
      Low discharge pressure in a Vertiv Heat Pump can be due to a faulty head pressure control valve or premium efficiency control board. If either is defective, replace it.

Summary

IMPORTANT SAFETY GUIDELINES

Save These Instructions

Manual contains important safety instructions for installation and maintenance of the Liebert MC unit.

Installation Safety Warnings

Covers risks of fan blades, electrical hazards, heavy lifting, and hot surfaces.

3 INSPECTION AND INSTALLATION

Safety Information

Crucial safety warnings regarding handling, lifting, and potential hazards during installation.

4 ELECTRICAL CONNECTIONS

Line Voltage Wiring

Instructions for connecting the unit's line voltage power supply, including wire size and protection.

Low-voltage Control Wiring

Details for CANbus communication and interlock wiring between indoor and outdoor units.

5 PIPING

Piping Guidelines

Best practices for installing refrigerant piping, including brazing and material selection.

7 INITIAL STARTUP CHECKS AND COMMISSIONING

Startup Checklist

Pre-startup verification steps to ensure all installation items are complete.

Initial Startup Procedures

Procedures for the first startup of the condenser, including fan rotation and air flow checks.

8 TROUBLESHOOTING

Troubleshooting Common Issues

Common symptoms, possible causes, and recommended checks or remedies for troubleshooting.

9 CONTROL OPERATION

Premium Efficiency Control Board and Interface

Description of the control board's layout, interface, and initial boot-up sequence.

Premium Efficiency Condenser Alarm Codes

Information on alarm codes, their meanings, and handling methods.

11 SYSTEM MAINTENANCE

General Procedures

Routine maintenance recommendations, including parts ordering and inspection intervals.

Condenser Cleaning

Instructions on how, when, and what to use for cleaning condenser coils for optimal performance.

Fan Replacement

Procedures and safety precautions for replacing condenser fans.

12 PREVENTIVE MAINTENANCE CHECKLIST

Vertiv Liebert MCL055 Specifications

General IconGeneral
BrandVertiv
ModelLiebert MCL055
CategoryHeat Pump
LanguageEnglish