Condenser
Models
Single Circuit Condensers Dual Circuit Condensers
Condensers
without
Liebert® Lee-
Temp
Condensers
with
Liebert®
Lee-Temp
Condensers with
Liebert®DSE or PDX-EEV Small
Receiver/Large Receiver*
Condensers
without
Liebert® Lee-
Temp
Condensers
with
Liebert®
Lee-Temp
Condensers with
Liebert®DSE Small
Receiver/Large Receiver*
Approximate R-410A Refrigerant Needed, lb/circuit (kg/circuit)
MCS028 2.5 (1.2) 21.7 (9.8) 11.0 (5.0) — — —
MCS056 — — — 2.5 (1.2) 21.7 (9.8) —
MCM040 3.5 (1.6) 22.7 (10.3) 12.0 (5.4) — — —
MCM080 8.5 (3.8) 39.8 (18.1) 17.0 (7.7) 3.5 (1.6) 22.7 (10.3) —
MCM160 — — — 8.5 (3.8) 39.8 (18.1) 17 (7.7) / 24 (10.9)
MCL055 5.0 (2.3) 24.2 (11.0) 13.5 (6.1) — — —
MCL110 10.7 (4.9) 49.1 (22.3) 19.5 (8.8) 5.2 (2.4) 24.4 (11.1) 14.0 (6.4)
MCL165 18.4 (8.4) 79.9 (36.2)
27.0 (12.2) /
34.0 (15.4)
— — —
MCL220 27.0 (12.3) 102.9 (46.7) 42.5 (19.3) 12.3 (5.6) 50.7 (23.0) 21.0 (9.5) / 28.0 (12.7)
*Small receiver (28 in. long) is used with DA050, DA080 and DA085; large receiver (60 in. long) is used with DA125, DA150 and DA165.
Source: DPN002411, Rev. 8
Table 5.5 Approximate Refrigerant Required, R-410A
Condenser Model
Single Circuit Condensers Dual Circuit Condensers
Condensers without
Liebert® Lee-Temp
Condensers with
Liebert® Lee-Temp
Condensers without
Liebert® Lee-Temp
Condensers with
Liebert® Lee-Temp
Approximate R-407C Refrigerant Needed, lb/circuit (kg/circuit)
MCS028 2.2 (1.0) 23.1 (10.5) — —
MCS056 — — 2.2 (1.0) 23.1 (10.5)
MCM040 3.0 (1.4) 23.9 (10.8) — —
MCM080 7.5 (3.4) 44.5 (20.2) 3.0 (1.4) 23.9 (10.8)
MCM160 — — 7.5 (3.4) 44.5 (20.2)
MCL055 5.0 (2.3) 25.9 (11.7) — —
MCL110 10.5 (4.8) 52.1 (23.7) 5.1 (2.3) 26.0 (11.8)
MCL165 18.3 (8.3) 84.8 (38.5) — —
MCL220 27.0 (12.3) 108.9 (49.4) 12.2 (5.6) 53.8 (24.4)
Source: DPN002411, Rev. 8
Table 5.6 Approximate Refrigerant Required, R-407C
Vertiv | Liebert® MC Installer/User Guide
30