Vitocell 300-H, EHA Series Technical Data
Technical Data
Technical Data
For domestic hot water heating applications which
utilize hot water heating boilers
Suitable for heating systems with:
H max. working pressure on heat exchanger
side up to 220 psig at 392°F (200°C)
H Only for 92 and 119 USG (350 and 450 L)
saturated steam 15 psig at 250°F (121°C)
H max. working pressure on DHW water side
of up to 150 psig at 210°F (99°C)
Storage capacity USG (L) 42 (160) 53 (200) 92 (350) 119 (450)
Recovery rates*1
with a temperature rise
water from 50 to 140°F
(10 to 60°C) and heating
water supply temperature of
. . . . . . at the supply flow
rate stated below
194°F MBH (kW)
(90°C) GPH (L/h)
96 (28)
126 (482)
113 (33)
150 (568)
239 (70)
318 (1204)
280 (82)
372 (1410)
176°F MBH (kW)
(80°C) GPH (L/h)
78 (23)
108 (396)
85 (25)
114 (430)
174 (51)
234 (877)
212 (62)
282 (1066)
158°F MBH (kW)
(70°C) GPH (L/h)
51 (15)
66 (258)
58 (17)
78 (292)
116 (34)
156 (585)
133 (39)
180 (671)
Supply flow rate
for the recovery rates stated GPM (m
3
/h) 13.2 (3.0) 22.0 (5.0) 22.0 (5.0) 22.0 (5.0)
Recovery rates *5
with a temperature rise of
the domestic hot water from
50 to 113°F (10 to 45°C)
a steam pressure of . . . .
and a max. steam velocity
of 164 ft/s (50 m/s)
7b psig MBH (kW)
GPH (L/h)
-- -- 283 (83)
539 (2039)
283 (83)
539 (2039)
15 psig MBH (kW)
GPH (L/h)
-- -- 358 (105)
682 (2580)
358 (105)
682 (2580)
Standby losses*2 MBH/24h 4.0 4.2 6.0 6.6
Overall dimensions
Overall depth
Overall width
Width without enclosure
Overall height
in. (mm)
in. (mm)
in. (mm)
in. (mm)
42a (1072)
25a (640)
--
25c (654)
48c (1236)
25a (640)
--
25c (654)
62b (1590)
32c (830)
30a (768)*3*4
31 (786)
65 (1654)
35c (910)
32 (810)*4
35 (886)
Weight
Tank with insulation lb (kg) 168 (76) 185 (84) 379 (172) 421 (191)
Heating water content
(heat exchanger pipe coil) USG (L) 1.8 (7) 2.1 (8) 3.4 (13) 4.2 (16)
Heat exchanger surface area ft
2
(m
2
) 9.36 (0.87) 9.7 (0.9) 18.3 (1.7) 22.6 (2.1)
Connections
Heating water supply/return
Domestic cold/hot water
Temp. and press. relief valve
7" (male thread)
7 (male thread)
7 (male thread)
1
c
c
1
c
1
1a
1a
1
1a
1a
1a
*1 When planning for the recovery rate as stated or calculated, allow for the corresponding circulation pump.
The stated recovery rate is only achieved when the rated output of the boiler is equal to or greater than that
stated under “Recovery rates”. Please also refer to the corresponding sizing chart at the end of this manual.
*2 Measured values are based on a room temperature of 68ºF (20ºC) and a domestic hot water temperature of
149ºF (65ºC) and can vary by ±5%.
*3 To overcome mechanical room access problems, the front panel with thermometer and side panels can be
removed, the adjustable feet unscrewed, and the Vitocell 300-H turned on its side.
*4 This is the net width of the Vitocell 300-H after removing the outer casing to ease problems of access into
the mechanical room.
*5 Only for 92 and 119 USG (350 and 450 L) saturated steam 15 psig at 250°F (121°C)