26
Vitovent
200-C 300-C 300-W
X — —
To compensate for systematic measuring errors, a
positive or negative adjustment value (offset) can be
set for the outdoor air temperature sensor.
Recommendation:
Set the "Standby mode" operating program. After
some time, compare the temperature values of all tem-
perature sensors against each other and/or against a
reference temperature. Set a corresponding correction
value for any deviating temperature sensors.
Setting 1 ≙ 0.1 K
7D77 Sensor matching, supply air temperature !
Vitovent
200-C 300-C 300-W
X — —
To compensate for systematic measuring errors, a
positive or negative adjustment value (offset) can be
set for the supply air temperature sensor.
Recommendation:
Set the "Standby mode" operating program. After
some time, compare the temperature values of all tem-
perature sensors against each other and/or against a
reference temperature. Set a corresponding correction
value for any deviating temperature sensors.
Setting 1 ≙ 0.1 K
7D79 Sensor matching, extract air temperature !
Vitovent
200-C 300-C 300-W
X — —
To compensate for systematic measuring errors, a
positive or negative adjustment value (offset) can be
set for the extract air temperature sensor.
Recommendation:
Set the "Standby mode" operating program. After
some time, compare the temperature values of all tem-
perature sensors against each other and/or against a
reference temperature. Set a corresponding correction
value for any deviating temperature sensors.
Setting 1 ≙ 0.1 K
7D83 Continuous operatn ON/OFF !
Vitovent
200-C 300-C 300-W
X X —
Value Meaning
"0" The "Continuous operation" operating pro-
gram can not be switched on.
"1" The "Continuous operation" operating pro-
gram can be switched on.
"2" The "Continuous operation" operating pro-
gram can be switched on.
7D84 Duration, economy mode !
Vitovent
200-C 300-C 300-W
X X X
Max. duration for "Economy mode"
Setting 1 ≙ 10 min
Parameter settings
7D76 Sensor matching, ODA temp downstream of preheat. coil !
5816558
Parameter