29
Vitovent
200-C 300-C 300-W
— X X
Set air flow rate for the "Standard" operating status in
the ventilation time program (ventilation level 3).
Set the design air flow rate from the engineering
parameters here.
Setting in m
3
/h
C10C Intensive ventilation !
Vitovent
200-C 300-C 300-W
— X X
Set air flow rate for the "Intensive" operating status in
the ventilation time program (ventilation level 4).
Setting subject to the building and engineering.
Standard setting values:
■
In the middle, between "Standard ventilation
C10B" and the max. air flow rate
Max. air flow rate
Installation and service instructions for the
connected ventilation unit
or
■
Approx. 30 % higher than "Standard ventilation
C10B"
Setting in m
3
/h
C1A0 Bypass operation !
Vitovent
200-C 300-C 300-W
— X X
How the bypass system works
Value Meaning
"0" Bypass can automatically be activated for
passive cooling.
Note
Further conditions must be met in order for
passive cooling to be switched on: See chap-
ter "Passive cooling" in the "Function descrip-
tion".
"1" The bypass is permanently closed. Heat re-
covery at the heat exchanger is switched on.
"2" The bypass is permanently active. Heat re-
covery at the heat exchanger is switched off.
C1A1 Central heating and heat recovery !
Vitovent
200-C 300-C 300-W
— X —
Do not adjust.
C1A2 Imbalance permitted !
Vitovent
200-C 300-C 300-W
— X —
Parameter settings
C10B Standard ventilation !
5816558
Parameter