Upper limit for air flow rate control depending on the
CO
2
concentration measured at CO
2
sensor 4:
If the measured CO
2
concentration is between "CO2
sensor 4 min PPM C1CE" and the set value, the ven-
tilation unit can automatically and continuously adjust
the air flow rate depending on the measured value.
Setting in ppm (parts per million)
7781 to 8687 Automatic changeover summertime - wintertime!
In the delivered condition, the changeover will always
take place in the night from Saturday to Sunday on the
last weekend in March and October. This setting can
be changed with the parameters "Summertime -
month", "Summertime - week", "Summertime -
day", "Wintertime - month", "Wintertime - week",
"Wintertime - day".
Parameter Delivered
condition
Setting range
"Automatic changeover summertime - win-
tertime 7781"
"1" "1" Automatic changeover enabled
"0" Automatic changeover not ena-
bled
"Start summertime - month 8682" "3" "1" to "12" January to December
"Start summertime - week 8683" "5" "1" to "5" First to last week of the month
"Start summertime - day 8684" "7" "1" to "7" Monday to Sunday
"Start wintertime - month 8685" "10" "1" to "12" January to December
"Start wintertime - week 8686" "5" "1" to "5" First to last week of the month
"Start wintertime - day 8687" "7" "1" to "7" Monday to Sunday
Parameter settings
C1CF CO2 sensor 4 max PPM !
5816558
Parameter