Conditions for passive cooling
Passive cooling ON Passive cooling OFF
All of the following conditions must be met:
Outdoor air temperature (heat exchanger air intake) is
< extract air temperature minus 4 K
Outdoor air temperature (heat exchanger air intake) is
> "Min. supply air temperature for bypass 7D0F"
plus 0.5 K
Extract air temperature > "Set extract air tempera-
ture 7D08" plus 1 K
One of the following conditions must be met:
Outdoor air temperature (heat exchanger air intake) is
extract air temperature minus 0.5 K
Outdoor air temperature (heat exchanger air intake) is
"Min. supply air temperature for bypass 7D0F"
plus 0.5 K
Extract air temperature "Set extract air tempera-
ture 7D08"
Passive cooling will not start if one of the following
conditions is met (bypass not active):
A sensor or fan fault has occurred.
Frost protection is active.
The electric preheating coil has been on in the last
10 min.
Frost protection
Defrost functions
The degree of icing up of the heat exchanger is moni-
tored. The selected defrost function is activated
according to the degree of ice formation: See following
table.
The determine the degree of ice formation the two fol-
lowing variables are observed and additional condi-
tions are taken into account, e.g. the installation posi-
tion of the ventilation unit ("Installation position
7D2F").
Fan speeds:
The pressure differential in the heat exchanger rises
with increasing ice formation. The fan speeds are
automatically increased to maintain a constant air
flow rate. From a certain speed onwards it is
assumed that the heat exchanger is iced up.
Supply air temperature:
The heat exchanger transfers less heat from the
extract air to the outdoor air due to ice formation.
The supply air temperature drops. From a certain
supply air temperature threshold onwards it is
assumed that the heat exchanger is iced up.
Monitoring of ice formation is active under the following
conditions:
The outdoor air temperature is below 2 °C.
No defrost function was active during the last 15 min.
The fans are switched on.
None of the temperature sensors in the ventilation
unit is faulty.
The defrost function is selected with the parameters
"Enable preheater bank electric 7D01" and "Strat-
egy, passive frost protection 7D2C".
Function description