Viessmann Solar?Divicon - Assembly and Installation Information; General Assembly Guidelines; Installation of Locking Ring Fittings

Viessmann Solar?Divicon
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
Assembly and installation information
H The Solar−Divicon comprises:
pre−assembled and sealed valves
and safety assembly
Flow regulating valve to control
the solar heating system during
the initial start−up and operation
Non−return valve in the flow and
return pipe
H Always install Solar−Divicon so that
steam cannot enter the expansion
vessel in the event of stagnation.
H The Solar−Divicon and the solar
circuit pump line are not suitable
for direct contact with swimming
pool water.
H Flush the system with process
medium after draining.
H If the expansion vessel is installed
as high or higher than the
Solar−Divicon, a thermal insulation
loop is required.
H A pre−cooling vessel connection is
fitted to the flow line to protect the
expansion vessel against excess
temperatures.
H Use only gunmetal, brass fittings,
copper pipes or Viessmann
stainless steel solar circuit pipes
for the installation. Never use
galvanized/zinc−plated pipes,
fittings or graphitised gaskets. Use
hemp only in conjunction with
pressure and temperature−resistant
sealants (e.g. ViscotexSolarpaste,
Locher & Co. AG, CH9450Altstätten).
Components that come in contact
with process medium must be
resistant to the medium.
H Check the sealing surfaces for
cleanliness and damage before
assembly.
Installation of the locking ring fittings
H All pipes must be cut at a right
angle and deburred.
H Insert the support sleeves into the
pipework.
H Push the union nut and the locking
ring onto the pipe and lightly
lubricate the threads with oil.
H Push the pipe into the locking ring
fitting as far as it will go.
H Initially turn the union nut by hand,
then tighten with an open ended
spanner by a further ¾ turn.
H Never fit annealed copper pipes
onto the locking ring fittings.
5862810GB