49
Appendix
Standard values for burner settings (cont.)
Gas throughput subject to the operational net calorific value (H
uB
) (cont.)
Gas
Gas
Rated boiler output
G
as
G
as
R
a
t
e
d
b
o
il
er ou
t
pu
t
type group
150 to 165 kW 190 to 210 kW
yp
gp
Boiler output
150 kW 165 kW 190 kW 210 kW
m
3
/h l/min m
3
/h l/min m
3
/h l/min m
3
/h l/min
Natural
E 17.3 289 19.0 318 21.9 366 24.2 405
Natural
gas
LL 20.1 336 22.1 370 25.4 424 28.1 470
Please note: Partial load gas throughput equals 60Ă% of full load gas